What is the difference between EI, EW and E fire-rated glass?

E blocks flames and smoke only. EW adds a limit on radiant heat. EI adds a limit on temperature rise on the unexposed face, so it is the only class that protects people in an adjoining corridor from heat.

The letters come from EN 13501-2. Integrity (E) means the glass stops flames and hot gases for the rated period. Radiation (W) means the radiant heat flux at 1 m from the surface stays under 15 kW/m². Insulation (I) means the average temperature on the unexposed face stays below 140 °C above ambient, with no single point above 180 °C.

In practice: use E in roof lights and places where nobody stands close; EW in facades and shopfronts where the fire brigade needs to approach; EI in escape corridors, stair enclosures and protected lobbies, because a person walking past an EW panel at minute 50 would still be burned by radiation.

Which standards and ratings apply to each class?

Classification standardEN 13501-2
Test standardsEN 1363-1, EN 1364-1, EN 1634-1
Typical ratingsE 30/60/120, EW 30/60, EI 15/30/60/120
Maximum EI height in one panelup to 3,000 mm with intumescent edge seal

Where do EI and EW get specified wrongly?

Related: Fire-rated glass Laminated glass Company fact sheet
Need a quote against your drawing?

Send the glass schedule, thickness build-up and destination port to info@cnglassworks.com or on WhatsApp (reply within 1 hour) / phone +86 138 3303 3053. A specification review and reference price come back within one working day.

Figures verified by the factory on 2026-11-02. Sizes are manufacturing limits, not project guarantees.

Price from USD ___ per sqm FOB Qinzhou, depending on thickness, coating and quantity.